WIRES & CABLES

ZHFR(Zero Halogen Flame Retardant)

Application

Wiring in all places where fire safety is necessity like schools, buildings, theaters, commercial complexes, apartments, laboratories, internal industrial wiring , etc.

Conductor

Thin strands of electrolytic copper having highest purity, least resistance are multi drawn for uniformity in dimension and flexibility.
There are two types by which thin copper conductors are bunched :
1.Traditional bunch conductor
2.Unilay bunch conductor

TRADITIONAL Bunch Conductor

UNILAY Bunch Conductor

Insulation

Specially formulated grade of Lead Free + Zero halogen + Flame Retardant (ZHFR) PVC compound is used for insulation. The insulation does not burn readily. It does not Melt and Drip, Smoke is negligible, Transparent, Non-Toxic. The trapped victims in fire do not suffocate and this facilitates fire fighting operations.

Benefits

Flame Retardant Property, High Temperature Resistant Insulation ,Non Corrosive And Non Toxic Insulation, Zero Toxic Shock In Fire Due To Lead Free Insulation, High Resistance For Moisture Preventing From Oxidation.

Marking

The cables are marked as "Masai Cables".

Colour

Red, Yellow, Blue, Black, Green, Grey.

Packing

90 meters coils packed in protective cartoons. Project coils of 180 meters also available in carry bags.

SINGLE CORE: SIZES, DIMENSIONS AND RATINGS

Conductor Area Insulation Thickness Number & Nominal Diameter of Strands Approx Overall Diameter DC Conductor Resistance (Ω /km) at 20°C (Max.) Current Rating
Unilay Flexible Wire Non Unilay Super Flexible Wire Non Unilay RM Wire Casing Consealed
Sq. mm mm Nos. / mm Nos. / mm Nos. / mm mm Ω / km Amps. Amps.
0.5 0.6 19 / 0.18 17 / 0.193 3 / 0.46 2.1 39.0 5 4.5
0.75 0.7 19 / 0.22 26 / 0.193 3 / 0.57 2.3 26.1 8 7
1 0.7 19 / 0.26 35 / 0.193 3 / 0.65 2.6 18.1 14 13
1.5 0.8 19 / 0.32 52 / 0.193 7 / 0.52 3.0 12.1 18 16
2 0.8 19 / 0.36 69 / 0.193 7 / 0.60 3.3 9.11 25 20
2.5 0.8 37 / 0.29 86 / 0.193 7 / 0.67 3.6 7.41 24 20
3 0.8 37 / 0.32 103 / 0.193 7 / 0.74 3.8 5.99 31 26
4 0.8 37 / 0.37 125 / 0.20 7 / 0.85 4.2 4.61 32 26
4.5 0.8 37 / 0.39 125 / 0.22 7 / 0.91 4.5 3.89 32 39
6 0.8 37 / 0.45 75 / 0.32 7 / 1.04 4.8 3.08 47 38
7 1 37 / 0.49 87 / 0.32 7 / 1.12 5.6 2.61 51 42
9.5 1 37 / 0.57 119 / 0.32 7 / 1.32 6.0 1.86 61 50
10 1 37 / 0.59 125 / 0.32 7 / 1.35 6.2 1.83 63 52
14.5 1 37 / 0.70 92 / 0.45 7 / 1.63 6.8 1.23 79 65
16 1 37 / 0.74 101 / 0.45 7 / 1.70 7.5 1.15 85 70

PROPERTIES :

Properties Test Method Value
Limited Oxygen Index ASTM - D 2863 > 32%
Limited Temperature Index ASTM - D 2863 > 250°C
Smoke Density (Light Absorption) ASTM - D 2843 < 10%
Acid Gas Generation
IEC - 60754 - 1 < 5%
 

All Domestic Cables we produce are Fire Retardant.